HXGN15-12/24/40.5KV High Voltage Fixed SF6 Ring Main Unit(RMU)

HXGN15 series is composed by standard finished function units from our company, it adopts advantaged FLN36 load break switch (LBS), use SF6 gas with superior performance as arcing insulating medium.It is small ,compact and convenient installation, safety, stable working.

It is widely used in 7.2~40.5kV electric power distribution system.

The switchgear meet the requirements of standard IEC62271-200,IEC62271-100 etc.

Product Highlights
  • Pressure release :There have two pressure release exits for bus room & cable room to ensure the pressure release under the condition of extreme to ensure person safety.
  • Three position/double position:Natural interlock switch, only in “Close “,”Earthing “ or “Interlock” 3 position
  • Interlock position:Switch is interlocked with operation structure to avoid misoperation High voltage cable room is interlocked with operation structure to avoid opening the installation door under the condition of switch non-grounding to protect person safety.
  • Panel Display:Panel analog primary circuit and clearly display that charge display can flash to display the electric parts. Five independently intervals to avoid the accident spread.

Overview

HXGN15 series is composed by standard finished function units from our company, it adopts advantaged FLN36 load break switch (LBS), use SF6 gas with superior performance as arcing insulating medium.It is small ,compact and convenient installation, safety, stable working.

It is widely used in 7.2~40.5kV electric power distribution system.

The switchgear meet the requirements of standard IEC62271-200,IEC62271-100 etc.

 

(NEW) HXGN15-12KV

 

Working Conditions
  1. Ambient temperature:-30℃ ~ +50℃;
  2. Altitude: Not exceed 2500m above sea level;
  3. Ambient humidity: Daily average RH ≤ 95%;
  4. Monthly average RH ≤ 90%
  5. Water vapor pressure:Daily average RH ≤ 2.2kPa; Monthly average RH ≤ 1.8kPa;
  6. Ambient environment: no fire, explosion danger, serious pollution, chemical corrosion and severe vibration place
Convenient Installation

Its small volume & light weight make user to install & delivery it more conveniently and easy . It can be completed wiring schemes according to user’s need, also can choose the intelligent control units to realize intelligent controlling & operation. Standard design make this product to be the best choice of users.

Simple Operation

Each switchgear has single line diagram(SLD) & analog displayer which can display inside parts. For operation, it has interlock board to guarantee the handle direction of rotation with correct operation. In order to avoid the operation in mistake, on the door, there has operation manual to supply & guarantee the simple & safe operation.

Structure Features
  • Appearance: its enclosure is used by cold –rolled steel or aluminium zinc plate mold. It is beautiful and high anti-erosion, compact ,small volume and convenient combination.The inner has five insulation intervals. The rear side has two pressure release exits.

  • Convenient installation: it can be assembled freely & simply as different design requirements. No special need for its installation size.

  • Maintenance –free: Good sealing,SF6 insulation gas pressure complies with IEC60298 standard, safe and reliable working, maintenance free.

Technical Parameters

product specification

No. Item Unit Parameter
1 Maximum system voltage kV 12 15 24 40.5
1 Rated voltage kV 7.2、11 13.8、15 17.5、20、22 30、33、36
2 Rated current A 630/1250
3 Rated frequency Hz 50/60
4 1min Power frequency withstand voltage Phase to phase, phase to earth kV 42 48 55 85
Fracture kV 48 55 65 95
5 Lightning impulse withstand voltage Phase to phase, phase to earth kV 75 90 125/150 170
Fracture kV 85 105 150/160 185
6 Short time withstand current Main circuit kA 25/2s
Earthing circuit kA 25/2s
7 Rated withstand current (peak) kA 63 50
8 Rated transferring current A 1300-1700
9 A 630
10 Rated cable(line) charging breaking current A Oct-50
11 No load transformer breaking current A 20
12 Cable charge breaking current in earthing fault A 100 80
13 Rated short circuit breaking current (peak) kA 20
14 Rated short circuit making current (peak) kA 63 50
15 Protection level IP4X
16 Load break switch life times 5000
17 Earthing switch life times 5000

Ordering Instructions

The following technical information is required at the time of ordering

  1. Main circuit scheme numbers, main wiring system diagrams, arrangement diagrams, and floor plans.
  2. Auxiliary circuit electrical schematic diagram, terminal arrangement diagram.
  3. Model, specification, quantity of components in switchgear
  4. Name and quantity of spare parts and accessories
  5. If there are special requirements, please consult with us before ordering.