DLW Series Intelligent Universal Type Air Circuit Breaker (ACB) (hereinafter referred to as Circuit Breaker) is suitable for AC 50Hz, rated voltage up to 660V (690V) and below, rated current 630A~6300A in power distribution network. The Circuit Breaker conforms to GB14048.2-2001 and IEC60947-2-1995 and other standards.
It is used to distribute electric energy and protect lines and power supply equipment from overload, undervoltage, short circuit, single-phase grounding and other fault hazards.
The Circuit Breaker has intelligent protection function and precise selective protection, which can improve the reliability of power supply and avoid unnecessary power outage. It also comes with open communication interface to meet the requirements of control center and automation system.
The Circuit Breaker has an impulse withstand voltage of 8000V at an altitude of 2000 meters above sea level (different altitudes are corrected according to the standard, and the maximum does not exceed 12000V above ground).
It has the functions of overload long delay anti-time limit, short delay anti-time limit, fixed time limit and instantaneous. Can be set by the user to compose the required protection characteristics;
Single-phase grounding protection function;
Display function: setting current display, action current display, the main display of each line voltage (voltage display should be proposed at the time of ordering);
Alarm function: overload alarm;
Self-test function: overheating self-test, microcomputer self-diagnosis;g. Test function: test the action haracterist ics of the controller.
The normal working conditions and installation conditions
Air temperature:
Ambient air temperature is -25℃~+70℃ (LC low temperature product is -45℃~+70℃), the average value of 24h is not more than +35℃, higher than +40℃ should be used with reduced capacity. Please refer to the table of coefficient of capacity reduction.
Atmospheric conditions:
The relative humidity of the atmosphere in the surrounding air temperature of +40 ℃ does not exceed 50%, at lower temperatures can have a higher relative humidity, the wettest month of the average maximum relative temperature of 90%. The monthly average maximum relative temperature of the wettest month is 90%, while the average minimum temperature of the month is +25℃, taking into account the condensation that occurs on the surface of the product due to temperature changes.
Altitude:
The altitude of the installation site should not exceed 2000m, and above 2000m, it should be used with reduced capacity.
Technical Parameters
Technical Parameters
Product Model
DLW1-1600
DLW1-2000
DLW1-3200
DLW1-4000
DLW1-6300
IEC 60947-2 GB/T14048.2
Current Shell Frame
nm(A)
1600
2000
3200
4000
6300
Rated Current
n(A)
200/400/630/800/1000
1250/1600
400/630/800/1000/1250/1600/2000
2000/2500/2900/3200
3200/3600/4000
4000/5000/6300
Number of Poles
3P/3PN/4P
3P/3PN/4P
3P/3PN/4P
3P/3PN/4P
3P/3PN/4P
Operation Frequency
(Hz)
50/60
Rated Working Voltage
Ue(V)
400/690
Rated Insulation Voltage
Ui(V)
1000
Rated Impulse Withstand
Voltage
Uimp(KV)
12
Rated Ultimate Short Circuit
AC400V
65
80
100
100
80
120
Breaking Capacity Icu(kA)
AC690V
50
65
75
75
65
85
Rated Service Short Circuit
Breaking Capacity Ics (kA)
AC400V
55
80
85
85
80
100
AC690V
42
65
75
75
65
85
Rated Short Time Withstand
AC400V
42
65
85
85
60
100
Current Icw(kA)
AC690V
35
50
75
75
50
85
Rated Chort Time Withstand
Current Icm(kA)
AC400V
143
176
220
220
176
264
AC690V
105
143
165
165
143
187
Operating Time(ms)
Disconnect
<30ms
Connect
≤60ms
Flying Arc Distance
0
Operational Performance
(Times)
Mechanical life
With Maintenance
30000
30000
20000
25000
15000
10000
Without Maintenance
15000
15000
75000
12500
6500
5000
Operating Frequency
60 times/hour
Electrical life
AC400V
10000(200~1000A)
8000(1250~1600A)
15000(400~800A)
14000(1000~1600A)
10000(2000A)
15000(2000~2500A)
12500(2900A)
10000(3200A)
6000
6000
1500
AC690V
10000(200~1000A)
5000(1250~1600A)
15000(400~1250A)
7000(1600A)
5000(2000A)
15000(2000A)
9000(2500A)
5000(2900~3200A)
4500
3000
800
Operating Frequency
20 times/hour
Isolation Function
■
■
■
■
■
Protection
Intelligent Controller(M Type)
■
■
■
■
N-level Protection Function(Only 3PN &4P)
□
□
□
□
□
Use and Installation
Operating Temperature
-25℃~+70℃ average value within 24h does not exceed +35℃(customization is required for exceeding this temperature range)
Operating Temperature
Ambient air temperature of +40℃,atmospheric relative humidity not exceding 50%,maximum relative humidity not exceding 90%at+20℃.
Altitude
≤2000m
Type of use
B
Installation Type
Main circuit
IV
Auxiliary,control circuit
Ⅲ
Pollution level
3
Connection method
Horizontal/Vertical
Horizontal/Vertical/Extension
Horizontal/Vertical/Extension
Horizontal
Horizontal
Installation method
Fixed Type
Draw-out Type
Fixed Type
Draw-out Type
Fixed Type
Draw-out Type
Fixed Type
Draw-out Type
Fixed Type
Draw-out Type
Width(W/W1)
260/330
275/345
340/435
375/470
400/515
435/550
537(3P)
550/812
802/886
816/895
Height(H)
310
345
402
425
402
425
402
432
405
432
Depth(D)
240
330
373
445
363
445
413
494
413
494
■Yes □Optional —No
Installation
Installation category
Rated operating voltage of 660V (690V) and below circuit breakers and undervoltage disconnectors, the primary coil of the power transformer is used for installation category IV; auxiliary circuits and control circuits are installed in category III.
Installation conditions
The circuit breaker shall be installed according to the requirements of this manual, and the vertical inclination of the circuit breaker shall not exceed 5 degrees (the inclination of the mining circuit breaker shall not exceed 15 degrees).
Fixed circuit breaker installation dimensions and external dimensions (DLW1-2000/3, 2000/4).
Fixed circuit breaker installation dimensions and external dimensions (DLW1-3200/3, 3200/4).
Drawer type circuit breaker installation dimensions and external dimensions
Drawer type circuit breaker installation dimensions and external dimensions (DLW1-2000/3, 2000/4)
Drawer type circuit breaker installation dimensions and external dimensions (DLW1-3200/3, 3200/4)
Installation dimensions and external dimensions of drawer type circuit breaker (DLW1-6300/3, 6300/4 In=4000, 5000A)
Installation dimensions and external dimensions of drawer type circuit breaker (DLW1-6300/3, In=6300/4)
Mounting dimensions and external dimensions of drawer type circuit breaker (DLW1-6300/3 In=6300A)
Distributed from door frame size and installation
Inm
a mm
b mm
c mm
2000
306
345
0
3200, 4000/3
366
405
0
4000/4
306
345
20
6300
366
405
20
FAQ
1. What is an Air Circuit Breaker and where is it used? An ACB is a high-capacity circuit breaker used in low-voltage power distribution systems (up to 690V), typically installed in main switchboards to protect against overloads, short circuits, and ground faults. It’s ideal for critical infrastructure, industrial plants, and commercial buildings.
2. What current range do your ACBs support? Our ACBs are available from 630A to 6300A, with common frame sizes including 1000AF, 1600AF, 3200AF, 4000AF and 6300AF. Each frame supports adjustable protection settings to suit various load profiles.
3. What trip unit types are available for your ACBs? We offer electronic trip units with full protection functions including LSI (Long-time, Short-time, Instantaneous) and optional ground fault protection. For advanced monitoring, communication-enabled trip units (Modbus/RS485) are also available.
4. Are your products certified for international export?
Absolutely. We manufacture in full compliance with IEC/EN 60947-2. We can also provide CE or other certifications based on the requirements of the target market.
5. Do you offer both fixed and draw-out type ACBs? Yes, we supply both fixed-mounted and draw-out (withdrawable) types. Draw-out models are widely used for ease of maintenance, system isolation, and backup switching in main distribution panels.
6. How do I choose the correct ACB for my project? Consider factors such as rated current, breaking capacity (Icu/Ics), pole configuration (3P/4P), trip settings, communication needs, and whether you require fixed or draw-out structure. Our technical team can assist with selection based on your SLD and project specs. You can also send your request to this email address (info@derlicn.com), or you can fill out the contact form on our product page.
7. What is the breaking capacity of your ACBs? Our ACBs support breaking capacities up to 100kA at 400/415V, depending on the frame size. This ensures safe interruption even in large fault current environments.
8. What’s the typical delivery lead time? Standard configurations can usually be shipped within 10–15 working days. For customized protection settings, OEM branding, or large volumes, lead time is around 20–30 working days.
9. What is your MOQ for ACB orders? We support trial orders starting from 1 unit. For OEM/ODM branding or special configurations, MOQs typically start from 10–50 units per model.
10. Do you support OEM/ODM services? Yes. We offer OEM services including your logo printing, custom color or panel design, and ODM services such as special trip unit programming, customized accessories, or housing design for strategic partners.
11. What is your warranty policy for ACBs? We offer a 12-month warranty from the shipping date. In case of functional defects under proper use, we provide free spare parts, technical support, or product replacement based on the situation.
12. What kind of after-sales support do you provide? We provide lifetime technical support, remote commissioning guidance, and if needed, video call assistance. For key markets, we can also recommend or coordinate with local service partners for onsite troubleshooting.
13. Do you provide communication-enabled ACBs? Yes. Our advanced ACB series supports Modbus-RTU communication, enabling remote monitoring, status checking, and event logging, which is critical for smart power management systems.
14. What payment terms do you accept?
We accept T/T and Alibaba Trade Assurance for online orders. Other options like PayPal can be considered for sample purchases.
15. Why should we choose your company as our ACB supplier? We are a trusted low-voltage switchgear manufacturer with over 14 years of experience in OEM/ODM export. Our ACBs combine robust protection, customizability, certified performance, and fast response support—backed by successful installations in 40+ countries.