DLM1E Series Adjustable Moulded Case Circuit Breaker (MCCB)

DLM1E Series Adjustable Moulded Case Circuit Breaker (MCCB) (hereinafter referred to as circuit breakers) are suitable for infrequent switching and infrequent starting of motor in circuits with AC 50Hz (or 60Hz), rated insulation voltage of 800V, rated working voltage of 690V and below, and rated working current of 800A.

The circuit breaker has overload long delay anti-time limit, short-circuit short delay anti-time limit, short-circuit short delay fixed-time limit, short-circuit instantaneous and under-voltage protection function as well as residual current protection (optional), phase-loss
protection function (optional), which can protect the line and power supply equipment from being damaged.

The protection characteristics of the circuit breaker are complete and accurate, which can improve the reliability of power supply and avoid unnecessary power outages, B” type control with communication interface, can be “four remote” to meet the requirements of the control center and automation system.

The circuit breakers can not be inverted into the line, that is, only allows 1, 3, 5 connected to the power line, 2, 4, 6 connected to the load line.

The circuit breakers are divided into two types according to their rated ultimate short-circuit breaking capacity: L-type (standard type), M-type (higher breaking type) and H-type (high breaking type).

Overview

Product Overview

DLM1E series electronic MoldedCase Circuit Breakers (hereinafter referred to as circuit breakers) are suitable for infrequent switching and infrequent starting of motor in circuits with AC 50Hz (or 60Hz), rated insulation voltage of 800V, rated working voltage of 690V and below, and rated working current of 800A.

The circuit breaker has overload long delay anti-time limit, short-circuit short delay anti-time limit, short-circuit short delay fixed-time limit, short-circuit instantaneous and under-voltage protection function as well as residual current protection (optional), phase-loss
protection function (optional), which can protect the line and power supply equipment from being damaged.

The protection characteristics of the circuit breaker are complete and accurate, which can improve the reliability of power supply and avoid unnecessary power outages, B” type control with communication interface, can be “four remote” to meet the requirements of the control center and automation system.

The circuit breakers can not be inverted into the line, that is, only allows 1, 3, 5 connected to the power line, 2, 4, 6 connected to the load line.

The circuit breakers are divided into two types according to their rated ultimate short-circuit breaking capacity: L-type (standard type), M-type (higher breaking type) and H-type (high breaking type).

The Circuit Breaker is characterized by small size, high breaking capacity, short flying arc, anti-vibrationand so on.

The Circuit Breaker can be installed vertically (i.e. vertically mounted) or horizontally (i.e. horizontally mounted).

The Circuit Breaker conforms to: IEFC60947-2, GB14048.2 standard.

Model

DLM1E Series Adjustable Moulded Case Circuit Breaker

Notes:

  1. According to the rated ultimate short-circuit breaking capacity of the product is divided into: L-type (standard), M-type (higher breaking type), H-type (high breaking type).
  2. No code for handle direct operation; Electric operation is indicated by P; Rotating handle is indicated by Z.
  3. No code for circuit breaker for power distribution; Motor protection is indicated by 2.
  4. According to the number of poles of the product is divided into 3 pole and 4 pole.
The Normal Working Conditions And Installation Conditions
  1. Altitude: <2000m;
  2. Maximum inclination is 22.5°;
  3. Ambient temperature: -5℃~ +40℃;
  4. In a medium with no danger of explosion, and the mediumis not sufficiently corrosive;
  5. Withstand the effects of humid air;
  6. Metal and insulation-destroying gases and conductive dust places;
  7. Withstand the effects of salt spray and oil mist;
  8. Where there is no rain or snow intrusion;
  9. Pollution class: 3;
  10. Installation category: ll.

Technical Parameters

Technical Parameters

Model Number DLM1-125 DLM1-250 DLM1-400 DLM1-630 DLM1-800
Current shell frame (A) 125 250 400 630 800
Setting current Ir1 (A) 25, 30, 32, 40, 50, 63, 80, 100, 125 100, 125, 140, 150, 160, 175, 180, 200, 225, 250 250, 300, 315, 320, 350, 400 400, 450, 500, 630 630, 700, 800
Rated insulation voltage (V) Ui 800 800 800 800 800
Rated impulse withstand voltage(kV)Uimp 8 8 8 8 8
Code for breaking capacity L M H L M H L M H L M H L M H
Rated ultimate short circuit breaking capacity (kA) 25 50 85 36 50 85 36 50 85 50 65 100 50 65 100
Rated service short-circuit breaking capacity (kA) 400V/690V 25 50 85 36 50 85 36 50 85 50 65 100 50 65 100
Rated service short-circuit breaking capacity Ics (%Icu) 100% 100% 100% 100% 100%
Cat A
Poles number 3, 4 3, 4 3, 4 3, 4 3, 4
Mechanical life(times) 20000 20000 10000 10000 5000
Electrical life(times) 3000 3000 3000 1500 1000
Flying Arc Distance(mm) ≤50 ≤50 ≤50 ≤100 ≤50
Accessories

Accessories of DLM1E Series Adjustable MCCB

Adjustment knob for DLM1E series electronic circuit breaker

DLM1E series circuit breaker overload long delay inverse time current Ir1, long delay time t1, short-circuit short delay current r2, short delay time t2, short-circuit instantaneous current Ir3, pre-warning current r0 each adjusting knob is as follows.

Adjustable Knob for DLM1E Series Adjustable MCCB

Installation Method

Installation Method
  1. Wiring in front of the board
    X-X, Y-Y for three-stage breaker center

Wiring in front of the board-DLM1E Series Adjustable MCCB

2. Shared excitation disconnectors
Connect to the power supply according to the number of the lead wire (DC power supply does not need to distinguish between positive and negative poles).

Share excitation disconnectors of DLM1E Series Adjustable MCCB

3. Auxiliary contact, alarm contact
According to the lead wire number access to the corresponding peripheral control circuits

Auxiliary contact & alarm contact of DLM1E Series Adjustable MCCB

Note: F11, F12, F14 for auxiliary contact terminals B11, B12, B14 for the alarm contact terminals.

Auxiliary contact & alarm contact of DLM1E Series Adjustable MCCB-1

Have you
Any Questions?

Can’t find an answer to your question, or want more information about our products? If so, please feel free to get in touch with our professional team. We’re here to help you drive your projects to success.

Contact us for a quotation