CJX2F Series AC Contactor

CJX2-F series AC contactors (hereinafter referred to as contactors) are mainly used in circuits with AC 50Hz or 60Hz, rated insulation voltage of 1000V, and rated current up to 800A at rated working voltage of 380V under AC-3 use category.
The AC contactors can be used to connect and disconnect circuits over long distances and can be combined with suitable thermal overload relays to form electromagnetic starters to protect circuits where operational overloads may occur.

The contactor can be used for frequent starting and control of AC motors.

The contactor is suitable for frequent starting and control of AC motor. The product conforms to GB14048.4 and IEC60947-4-1 standards.

Overview

Product Model

CJX2-F AC Contactor

The Normal Working Conditions And Installation Conditions
  • Ambient air temperature: -5℃ +~40℃ , the average value of which does not exceed +35℃ within 24 hours.
  • Altitude: not more than 2000m.
  • Atmospheric conditions: maximum temperature of +40 ℃ , the relative humidity of the air does not exceed 50%; at lower temperatures can be allowed to have a higher relative humidity, such as +20 ℃ up to 90%, due to temperature changes occasionally produce condensation should take special measures.
  • Pollution level: Class 3
  • Installation category: Class III.
  • Installation conditions: The inclination of the mounting surface to the vertical is not more than ± 5°.
  • Shock and vibration: The product should be installed and used in a place where there is no significant shaking, shock and vibration.
Characteristics of the structure

 

General Structure Diagram Of CJX2-F115~F265 AC Contactor

  • The contact system of the AC contactor is a true-action, double-breakpoint arrangement, the lower base is made of aluminum alloy, the coil is a plastic encapsulated structure, and the coil and the yoke form an integrated unit, which can be directly removed from the contactor or loaded into the contactor, and is extremely easy to use and maintain;.
  • The contactor can be equipped with two auxiliary contact groups, that is, 8 more pairs of contacts.
  • Contactor flying arc distance is small. Such as CJX2-F115 ~ F330 flying arc distance is only 10mm (200 ~ 500V), only one-sixth of other contactors of the same capacity.
  • Used in complete sets of equipment can reduce the space occupied, is an excellent supporting components in the electronic control equipment.
  • It can be installed with auxiliary contacts, air delay head and other accessories in a block type installation.
  • The AC contactor can be equipped with horizontal or vertical mechanical interlock.
  • Can be made into two, three, four-pole contactors.

Technical Parameters

Main parameters and technical performance
Model Appointment of Heat
Generation
Current(A)
Rated Operating Current(A) Controllable Three-phase Squirrel Cage
High Power of Notor (kW)
Operation
Frequency
Times/h
(AC-3)
AC-3
Electrical
life
(10,000
times)
Mechanical
Life time
(10,000
cycles)
Selected
Fuse
(SCPD)
Individual Weight
(kG)
AC-3 AC-3
380V 660V 1000V 380V 660V 1000V Model 2P 3P 4P
CJX2-F115 200 115 86 46 55 80 65 600 60 300 RT16-1 3.6 4.3
CJX2-F150 200 150 107 50 75 100 65 600 60 300 RT16-1 3.7 4.5
CJX2-F185 275 185 118 71 90 110 100 600 50 300 RT16-2 4.6 5.4
CJX2-F225 275 225 135 90 110 129 100 600 50 300 RT16-2 4.7 5.7
CJX2-F265 315 265 170 112 132 160 147 600 50 300 RT16-2 7.1 8.5
CJX2-F330 380 330 225 155 160 220 160 600 50 300 RT16-3 8.5 10
CJX2-F400 450 400 235 200 200 280 185 300 30 100 RT16-3 7.3 8.5 10
CJX2-F500 580 500 290 232 250 330 315 300 30 100 RT16-4 9.1 10.8 12.9
CJX2-F630 800 630 360 331 335 450 425 300 20 100 RT16-4 14.1 17.4 20.5
CJX2-F780 830 780 440 400 400 470 450 300 20 100 RT16-4 23.5 40
CJX2-F800 860 800 450 415 400 470 450 300 20 100 RT16-4 19
CJX2-F1250 1260 300 20 100 RT16-4 18.2

Action Characteristics:
Suction voltage: 85%-110%Us, release voltage: 20%-75%Us

Main Specification Designation of Coils
Model Control Voltage (V) Average power consumption
(20℃)
Weight
(kG)
110V 127V 220V 380V Suction (VA) Holding (VA)
CJX2-F115、F150 Ff110 Ff127 Ff220 Ff380 550 45 0.44
CJX2-F185、F225 FG110 FG127 FG220 FG380 800 55 0.5
CJX2-F265 FH110 FH127 FH220 FH380 1200 13 0.73
CJX2-F330 FH110 FH127 FH220 FJ380 1200 13 0.84
CJX2-F400 FJ110 FJ127 FJ220 FJ380 1200 20 0.96
CJX2-F500 FK110 FK127 FK220 FK380 1250 24 1.1
CJX2-F630 FL110 FL127 FL220 FL380 1650 22 1.3
CJX2-F780 FX110 FX127 FX220 FX380 2100 50 2.6
CJX2-F800 Fl110 Fl127 F|220 Fl380 1650 22 1.5
CJX2-F1250 FL110 FL127 FL220 FL380 1650 22 1.3
Ability to connect wires
Model CJX2-F115 CJX2-F150 CJX2-F185 CJX2-F225 CJX2-F265 CJX2-F330 CJX2-F400 CJX2-F500 CJX2-F630 CJX2-F780 CJX2-F800 CJX2-F1250
Number of wires 1 1 1 1 1 1 2 2 2 2 2 2
Wire cross section (mm²) 95 120 150 185 240 240 150 240 240 240 240 240
Number of wires 2 2 2 2 2 2 2 2 2 2 2 2
Copper row (mm) 20×3 25×3 25×3 32×4 32×4 30×5 30×5 40×5 60×5 60×5 60×5 60×5
Connecting bolt M6 M8 M8 M10 M10 M10 M10 M10 M12 M12 M12 3×M12

Installation Dimension

Installation Dimension unit(mm)
MODEL CJX2-F115 CJX2-F150 CJX2-F185 CJX2-F225 CJX2-F265 CX2-F330 CJX2-F400 CJX2-F500 CJX2-F630 CJX2-F800 CJX2-F1250
3P 4P 3P 4P 3P 4P 3P 4P 3P 4P 3P 4P 2P 3P 4P 2P 3P 4P 2P 3P 4P 3P 3P
Amax 167 204 167 204 170 211 170 211 202 247 218 261 215 215 261 235 235 288 310 310 389 310 310
Bmax 163 163 171 171 175 175 175 175 203 203 210 210 210 210 210 240 240 240 304 304 304 304 304
Cmax 172 172 172 172 183 183 183 183 215 215 223 223 223 223 223 235 235 235 257 257 257 257 257
P 37 37 40 40 40 40 48 48 48 48 48 48 48 48 48 55 55 55 80 80 80 80 80
S 20 20 20 20 20 20 25 25 25 25 25 25 25 25 25 30 30 30 40 40 40 40 40
Φ M6 M6 M8 M8 M8 M8 M10 M10 M10 M10 M10 M10 M10 M10 M10 M10 M10 M10 M12 M12 M12 M12 M12
f 131 131 131 131 131 131 131 131 147 147 147 147 147 147 147 150 150 150 181 181 181 181 181
M 147 147 150 150 154 154 172 172 178 178 181 181 181 181 181 208 208 208 264 264 264 264 264
H 124 124 124 124 127 127 127 127 147 147 158 158 158 158 158 172 172 172 202 202 202 202 202
L 107 107 104 107 113.5 113.5 113.5 113.5 141 141 145 145 145 145 145 146 146 146 155 155 155 155 155
X1 200~500V 10 10 10 10 10 10 10 10 10 10 10 10 15 15 15 15 15 15 20 20 20 20 20
X1 660~1000V 15 15 15 15 15 15 15 15 15 15 15 15 20 20 20 20 20 20 30 30 30 30 30
Ga 80 80 80 80 80 80 80 80 96 96 96 96 80 80 80 80 80 80 180 180 180 180 180
Ha 106/119 106/119 106/119 106/119 106/119 106/119 170/180 170/180 180/190 180/190 180/190

Notes.

  • f: Minimum distance required to take out each coil.
  • x1: Flying arc distance determined by operating voltage and breaking capacity.

Dimension of CJX2-F AC Contactor-1 Dimension of CJX2-F AC Contactor-2

 